City of Adelanto (CA)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2025 CALIFORNIA BUILDING CODE
2025 CALIFORNIA ELECTRICAL CODE
2025 CALIFORNIA FIRE CODE
2025 CALIFORNIA PLUMBING CODE
2025 CALIFORNIA MECHANICAL CODE
2025 CALIFORNIA ENERGY CODE
2025 CALIFORNIA RESIDENTIAL CODE
2025 CALIFORNIA ADMINISTRATIVE CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Adopted
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- MPU,Derate
- How Many Plansets Required
- Other (See Submission Notes)
- Revision Required
- 1
- Rough Inspection
- None
- New Planset Required For Module Swap
- 1
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- None
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Provide a 3 foot pathway measured perpendicular from the exterior wall. In other words, if the overhang is 1 foot, provide a 4 foot pathway measured from the edge of the roof overhang (flying rafter) Panels and modules installed on dwellings shall not be placed on the portion of a roof that is below a bedroom window. A 36-inch-wide pathway shall be provided to the window opening.
Structural & loads
- Wind Speed
- 110
- Wind Notes
Exposure Category C
- Snow Load
- 5
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 48
- Minimum Ground On Roof
- #10
Electrical
- AC Disconnect Conditional Criteria
- Exterior knife switch required
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Meter Adapter,Load Side Taps,Line Side Taps,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
- BOS Restrictions
Standard
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Provide an elevation diagram showing the ESS will be minimum 3 feet from doors, windows, and other ESS.
ESS disconnect required within 6ft of Battery on same wall and not blocked by walls/gates/etc
IF ESS IS TO BE LOCATED IN A GARAGE THEN A DETAILED FLOOR PLAN MUST BE PROVIDED SHOWING THAT THE ESS IS NOT WITHIN THE DRIVING PATH OF THE VEHICLE
The maximum energy capacity of individual ESS units shall not exceed 20 kWh. • The ESS shall comply with applicable requirements in Section 1207. • The ESS shall be installed in accordance with the manufacturer's instructions and their listing. • Individual ESS units shall be separated from each other by at least 3 feet (914 mm). • The ESS shall be separated from doors, windows, operable openings into buildings or HVAC inlets by at least 3 feet (1524 mm). [CFC 1207.8.4]
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- Yes - with dimensions
Plan set
- Plan Set Requirements
- Cover Page
Notate whether or not the project will contain solar energy storage (ESS)
- Site
Demonstrate or note the size of the roof overhang for the AHJ to confirm that our fire access pathway does not extend onto the unsupported section of roof past the load bearing walls.
- Site Notes
Specify if license is C-10 or C-46. Each sheet of plans shall bear the name, license number, signature, and date of a C-46 (solar license) or a C-10 (electrical license) as the design-builder of the photovoltaic solar system.
Do this on the title block
- Roof Plan
Show dimensions of PV array
- Attachment Detail
Provide wind speed on attachment detail page
- Electrical Diagram
120% rule allowed per CEC 705.12(B)(2)(3)(d)
TLD needs to show an exterior knife switch Include note: DC disconnect and AFCI included next to inverter.
When performing a service upgrade, provide a surge protection device and call it out on the line diagram.
- Custom Placards Required
- 1
Ground mount
- Ground Mount Fencing Required
- No
- Ground Mount Notes
Can't be seen from the street. Setbacks are 10' from rear & 5' from sides. Spoke with the inspector Greg.
- Setback Back Yard
- 10
- Setback Side Yard
- 5