City of Manteca (CA)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2025 CALIFORNIA BUILDING CODE
2025 CALIFORNIA ELECTRICAL CODE
2025 CALIFORNIA FIRE CODE
2025 CALIFORNIA PLUMBING CODE
2025 CALIFORNIA MECHANICAL CODE
2025 CALIFORNIA ENERGY CODE
2025 CALIFORNIA RESIDENTIAL CODE
2025 CALIFORNIA ADMINISTRATIVE CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Testing
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- MPU,Derate
- How Many Plansets Required
- 3
- Revision Required
- 1
- Rough Inspection
- None
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- Yes - Derate
- Wet Stamps Required
- None
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 110
- Wind Notes
Exposure Category B
- Snow Load
- 0
- Snow Load Notes
N/A
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 48
- Structural Notes
STRUCTURAL CALCS REQUIRED IF: * All tile roofs * Comp roof with more than 4' attachment spacing and/or more than 5 PSF Ground mount PV system requires engineering analysis for seismic and wind loads, provide analysis for the ground mount structure
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates,Taps
- Allowed POI
- Line Side Taps,PV Breaker,Load Side Taps,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 75
- De Rating Ampacity
- 0.96
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Indicate clearly on the drawings and in references, if the ESS is to be used during 'ON GRID' operation to shift PV generation from 'TIME OF USE', or if the ESS will operate and provide provide electricity, "OFF GRID".
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
Layout of panels needs to reflect a straight egress path from 2nd story windows to the edge of the roof.
At lower front roofs: PROVIDE A CLEAR PATH FOR EGRESS THE WIDTH OF THE OPENABLE / OPERABLE SIDE OF THE WINDOW. THIS PATH OF EGRESS SHALL BE MAINTAINED FROM THE WINDOW DOWN TO THE LOWER GUTTER
MUST include picture showing if panel is end fed (120% of bus rating) or centerfed( 120% of bus rating) plan set must include 1-2 pics of main panel show inside wiring
CE will need to flatten plans prior to uploading.
- Site
Mean roof height to be included on Site Plan
- Roof Plan
Layout of panels needs to reflect a straight egress path from 2nd story windows to the edge of the roof.
- Attachment Detail
* **09/22/21 - DERATING** **Provide load calculations for the derating of the main breaker. Show that the proposed main breaker is sufficiently sized for the existing loads present at the residence.**
- Electrical Diagram
120% rule allowed per CEC 705.12(B)(2)(3)(d) For all taps: identify how the tap connection will be made, where it will be made, and with what product. Provide a cut sheet for the product.
- Label Page
* **09/22/21 - LABEL PANEL** **Indicate on the plans that a label is to be placed at the main breaker panel** **stating: " MAIN BREAKER HAS BEEN DOWNSIZED TO ACCOMMODATE SOLAR, DO NOT UPSIZE ABOVE 150 AMPS"**
- Label Page Notes
If derating, include following placard. "MAIN BREAKER HAS BEEN DOWNSIZED TO ACCOMMODATE SOLAR, DO NOT UPSIZE ABOVE XXX AMPS"
ADD NOTE ON PLACARD: CAUTION: DO NOT ADD OR ALTER ELECTRICAL LOADS BETWEEN MAIN BREAKER AND NON-PV END OF BUSSING WITHOUT THE APPROVAL OF AN ELECTRICAL ENGINEER
- Custom Placards Required
- 1
- Placards Notes
Placards required when disconnect is behind gate.
Ground mount
- Ground Mount Fencing Required
- Situational
- Ground Mount Notes
On ground-mounts: fencing not required for residential, but fencing is required for commercial Ground mount PV system requires engineering analysis for seismic and wind loads, provide analysis for the ground mount structure ***For Requesting Septic Map/ Plot Plans*** and request plans
- Setback Front Yard
- 5
- Setback Back Yard
- 5
- Setback Side Yard
- 5