City of Placentia (CA)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2025 CALIFORNIA BUILDING CODE
2025 CALIFORNIA ELECTRICAL CODE
2025 CALIFORNIA FIRE CODE
2025 CALIFORNIA PLUMBING CODE
2025 CALIFORNIA MECHANICAL CODE
2025 CALIFORNIA ENERGY CODE
2025 CALIFORNIA RESIDENTIAL CODE
2025 CALIFORNIA ADMINISTRATIVE CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Testing
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- Storage Systems,Existing Systems,Trenching,MPU,Derate
- How Many Plansets Required
- 2
- Revision Required
- 1
- New Planset Required For Module Swap
- 0
Stamps
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
- 2018 FIRE SETBACKS
- Provide the size of roof overhang. Provide a 3' plus the roof overhang size of pathway measured from the edge of the roof overhang (flying rafter). Or 3' pathway from the load bearing walls. Example If the roof overhang is 2', provide 5' pathway.
- Ensure and show that fire access pathway is a minimum of 3' at all points along the roof. Example show 3' pathway along ridge even if we are not installing on adjacent mounting plane.
- Ensure that the pathway does not cross over any roof obstructions.
- INCLUDE NOTE - 8" clearance from the module's edge to the roofing edge.
Structural & loads
- Wind Speed
- 110
- Wind Notes
Exposure Category B
- Snow Load
- 0
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- Structural calcs shall show all formulas used for addressing the vertical and lateral stability of the modules supports, including the wind uplift forces and the quantities of parameters used with references to corresponding codes sections.
- The structural calculations shall comply with NDS Sec. 12.2.1.1
- The length of the tapered tip of the bolts/screws have SHALL NOT IGNORE the required lag's embedment into the framing members.
- Minimum Ground On Roof
- #10
Electrical
- AC Disconnect Required
- Yes
- Electrical Load Calcs Required
- All Jobs
- Allowed POI
- Meter Adapter,Load Side Taps,PV Breaker,Line Side Taps
- Panel Schedule Required
- Partial Home Backup
- Service Ground Requirements
If the existing system is not in compliance, we must provide instruction to address method to fix the existing grounding system if it is not in compliance with the current CEC requirements.
- Temperature Rating
- 90
- De Rating Ampacity
- 0.96
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
ESS disconnect required within 6ft of MSP on same wall and not blocked by walls/gates/etc
ESS Elevation with attachment method for battery to be stamped as well
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- Yes - with dimensions
Plan set
- Plan Set Requirements
For MPUs - Provide spec sheet of MPU type and Bus rating
List the license class of the contractor below the license #. "Class: B, C-10, C-46"
- Site
- Roof Plan Notes
All Jobs [8" clearance from the module's edge to the roofing edge.]
Specify roof over hang size
Specify if home is protected by fire sprinklers
Provide existing system in total roof coverage calculations
- Attachment Detail
DELETE THE ATTACHMENT DETAIL ILLUSTRATION
Show that mounting system will be UL 2703 compliant. Add Certificate-of-Compliance to cut sheets.
48" max attachment span
- Attachment Detail Notes
All Jobs [THE INSTALLATION OF THE PV MODULES SHALL BE PER MANUFACTURER'S INSTRUCTION // WOOD SCREWS OR LAGS SHALL BE STAINLESS STEEL // MAXIMUM SPACING OF 18" BETWEEN THE ROOF AND PV MODULES]
- Electrical Diagram
INCLUDE LEADER POINTING TO GROUNDING ELECTRODE INDICATING -(N) 5/8 copper, L=8' electrode to be installed min 6' away from existing ground. Connect the existing and new grounds with #6 conductor together
- Electrical Diagram Notes
All Jobs [GROUNDING SYSTEM SHALL BE IN COMPLIANCE WITH 2025 CEC REQUIREMENTS]
- Label Page
Provide address on placard.
- Label Page Notes
All Jobs [SIGNAGE WILL BE UL 969 COMPLIANT]
- Custom Placards Required
- 1
- Non Standard Planset Requirements
- BOS Elevation
- Non Standard Revision Requirements
PROVIDE A DETAILED NARRATIVE LETTER, DO NOT USE ABBREVIATIONS LIKE 'BOS', ETC.
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim