City of Ukiah (CA)

California Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusAdopted
Wet Stamps RequiredNone
Fire Setback Enforced1

Codes

NEC Code Version
2023
Fire Code Version
2018 Building Code
Code List

2025 CALIFORNIA BUILDING CODE

2025 CALIFORNIA ELECTRICAL CODE

2025 CALIFORNIA FIRE CODE

2025 CALIFORNIA PLUMBING CODE

2025 CALIFORNIA MECHANICAL CODE

2025 CALIFORNIA ENERGY CODE

2025 CALIFORNIA RESIDENTIAL CODE

2025 CALIFORNIA ADMINISTRATIVE CODE

IEBC Accepted
1
ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Adopted
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
Existing Systems,Trenching
How Many Plansets Required
4
Revision Required
0
New Planset Required For Module Swap
0

Stamps

Wet Stamps Required
None
Structural Calculations Required
No
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes

Standard

Structural & loads

Wind Speed
110
Wind Notes

Exposure Category B

Snow Load
0
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes
If Utility is City of Ukiah, SE is required. ****_Update 7/21/21: staff, head building inspector, says they _allow breaker tie in_ as of July 2021_****
Minimum Ground On Roof
#10

Electrical

Electrical Load Calcs Required
Derates
Allowed POI
Line Side Taps,Meter Adapter,Load Side Taps,PV Breaker
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
0.91

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

Standard

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
No

Plan set

Plan Set Requirements

Add note on Site Plan: The Lockable fused disconnect must be within 10' of the Service Entrance Panel and must be accessible to the City at all times 24 HOUR UNRESTRICTED ACCESS See Placard requirements attachment for additional placard requirements SLD: NOTE: OPTION AVAILABLE FOR BOTH OH & UG SEALABLE GUTTER 8 X8 X16 MINIMUM POLARIS CONNECTORS TO BE USED FOR GUTTER BOX CONNECTIONS Wind Exposure: B or C Snow Load: No snow load unless above 1,300 foot elevation

Electrical Diagram

City of Ukiah does NOT allow the line side tap to be in the customer panel. Only allow the solar to feed directly onto the grid BREAKER TIE IN ALLOWED

Label Page

**City of Ukiah Utility jobs:**

Ground mount

Ground Mount Fencing Required
Mesh/Scrim