County of Napa (CA)

California Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusTargeted
Wet Stamps RequiredDigital Electrical
Fire Setback Enforced1

Codes

NEC Code Version
2023
Fire Code Version
2018 Building Code
Code List

2025 CALIFORNIA BUILDING CODE

2025 CALIFORNIA ELECTRICAL CODE

2025 CALIFORNIA FIRE CODE

2025 CALIFORNIA PLUMBING CODE

2025 CALIFORNIA MECHANICAL CODE

2025 CALIFORNIA ENERGY CODE

2025 CALIFORNIA RESIDENTIAL CODE

2025 CALIFORNIA ADMINISTRATIVE CODE

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Targeted
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
MPU,Derate
How Many Plansets Required
3
Revision Required
1
New Planset Required For Module Swap
1

Stamps

Ee Stamp Required On SLD
Yes
Wet Stamps Required
Digital Electrical
Structural Calculations Required
No
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes

Standard

Structural & loads

Wind Speed
110
Wind Notes

Exposure Category C

Snow Load
0
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes
Structural calculations only required if array is more than 24 inches from roof surface to bottom of array (very rare)
Minimum Ground On Roof
#10

Electrical

AC Disconnect Required
Yes
Electrical Load Calcs Required
Derates
Allowed POI
Load Side Taps,PV Breaker,Meter Adapter,Line Side Taps
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
0.96

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

This AHJ requires the elevation view.


Verify that ESS is located a minimum of 3' from all doors and windows in accordance with CFC 1207.11.3. or Note spacing/separation distance between ESS units. Ensure that spacing is compliant with CFC 1207.11.2.1 or UL9540A large-scale fire testing


No published information about battery placement. If battery system, include this note on ELD: Producer's storage device(s) will not cause the Host Load to exceed its normal peak demand. Normal peak demand is defined as the highest amount of power required from the Distribution System by Producer's complete facilities without the influence or use of the energy storage device(s).

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
Yes

Plan set

Plan Set Requirements

The plan set PDF needs a bookmark on each page, including all spec sheet pages. Bookmark Instructions: https://www.countyofnapa.org/DocumentCenter/View/24064/How-to-Add-a-Bookmark?bidId=

Site

All structures on property need to be identified on the site plan

Electrical Diagram

Standard

Custom Placards Required
1
Non Standard Revision Requirements

Clouding needs to be in red.

Ground mount

Ground Mount Fencing Required
Yes
Ground Mount Notes

SEPTIC SYSTEM NEEDS TO BE TO-SCALE AND HAS TO BE CLEARLY DEPECTICED ON THE PLANS.


Update the building site plan to clearly and accurately show/label the entire location of the existing onsite wastewater treatment system(s) and water system(s) to scale in feet. Include all the following features:

• septic tank(s)

• sump tank (if applicable)

• sewer line(s)

• leach lines/dispersal area

• septic reserve

• water source(s) (wells, springs, public water source connection, etc.)


Be sure to show the staging area for this project relative in feet to the improvements as referenced above.  


Please accurately show the location of existing and or proposed electrical conduit lines with a minimum 12” spacing from sewer components and water lines. 


* FENCE IS NEEDED FOR ALL GROUND MOUNTS * ADD NOTE TO PLANS FOR GROUND MOUNTS "10' BRUSH FREE ZONE REQUIRED AROUND ARRAY" * All wiring installed underground shall be suitable for wet locations and shall be clearly labeled as such on the conductor insulation. * All underground utility trenching shall be a minimum of 18” below grade, unless through or within a vineyard where a minimum depth of 48” shall be required as per County of Napa ordinance. Depth shall be measured from top of pipe or conduit to grade. * Provide two (2) ground rods spaced a minimum of 6’ apart if proof of a UFER ground cannot provided in the field * Provide all labeling as required by CEC, including a label stating “this service is being fed by multiple energy sources” (list all sources I.E. Service provider, PV system, generator etc.) and show the locations of each including all disconnects. * Unprotected grounding electrode conductors shall be a 6 AWG or larger copper or aluminum and shall be securely fastened to the construction. Grounding electrode conductors smaller than 6 AWG shall be protected ****For acquiring Septic map and plot plans**** and/or ###

Compiled from public records, 2026. Requirements change with code cycles and local amendments. Verify with the County of Napa (CA) building department before you rely on this, and treat it as a research head start, not a ruling. Getting quotes? Run them through the quote checker first.