City of Doral (FL)
Codes
- NEC Code Version
- 2020
- Fire Code Version
- 2018 Building Code
- Code List
2023 8TH EDITION FLORIDA BUILDING CODE: BUILDING
2023 8TH EDITION FLORIDA BUILDING CODE: RESIDENTIAL
2023 8TH EDITION FLORIDA BUILDING CODE: MECHANICAL
2023 8TH EDITION FLORIDA BUILDING CODE: PLUMBING
2023 8TH EDITION FLORIDA BUILDING CODE: FUEL GAS
2023 8TH EDITION FLORIDA BUILDING CODE: ENERGY CONSERVATION
2023 8TH EDITION FLORIDA BUILDING CODE: EXISTING BUILDING
2023 8TH EDITION FLORIDA BUILDING CODE: ACCESSIBILITY
2023 8TH EDITION FLORIDA FIRE PREVENTION CODE (NFPA)
2020 NATIONAL ELECTRIC CODE (NEC)
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Targeted
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- MPU,Derate
- Revision Required
- 1
- Rough Inspection
- Footing inspection
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- Yes
- Wet Stamps Required
- Digital Structural,Digital Electrical
- Structural Calculations Required
- Yes
- Ee Stamp Notes
Digitally Verified Signature
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
4'-6'' setbacks at ridge, gables and flat roof.
Structural & loads
- Wind Speed
- 175
- Wind Notes
Exp Cat C
- Snow Load
- 0
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- For Digitally signed documents: Create one PDF file per discipline to contain the corresponding drawings, ex: S-1, S-2, S-last in one STRUCTURAL PDF file, and same for ELECTRICAL.
- *ZIP Files are not acceptable file formats and thus not allowed for uploading.
- Apply a seal and date in the title block of all pages.
- Check document security and only leave restrictions for changing and assembling the document.
- Apply your verifiable digital signature by a trusted Certificate Authority.
- One PDF per disci_x0002_pline/trade NOTE: Each REWORK submittal MUST contain the entire BATCH of drawings.
- PDF files shall only have one layer (flattened) without any embedded objects.
- Do not flatten after signature has been applied.
- All security settings must be unrestricted for city to apply validation and review stamps. PDF files shall not be encrypted, password protected and must allow mark-ups.
- Scanned documents should be scanned at no less than 300 dpi.
- Plans must be submitted as one batch set per discipline, each page showing seal, and each set digitally signed by the design professional. Drawings must contain a scale.
- All drawings should have the same X/Y axis at (0,0) to allow overlay of drawings for an effective review.
- Electrical calculations shall be grouped with corresponding electrical drawings in one PDF file per discipline (consecutive order with cover page as the first page).
- Structural and Energy calculations to be saved and uploaded in individual PDF files. One per each discipline. a. All pages belonging to one NOA or a Florida approval shall be grouped into one PDF. The cover, details, and all components to be used shall be properly marked and be together in one PDF. No isolated pages should be submitted. Prepare one PDF for each NOA.
- All drawings must be Digitally signed and sealed using a third party trusted agency. If uploading a multi-page PDF, it shall be sufficient for the architect or interior designer to apply their digital signature and seal to the Cover or First Sheet of that bound set, as long as an accurate Index of Drawings, listing all the sheets, with their sheet number and latest revision date, which are intended to be signed and sealed, is included within that Cover or First Sheet. For Engineers, only
- The Building Department adds a Reviewed for Compliance dated stamp to each page within the set of plans and support documents. Please ensure that you leave a 2โ x 12โ rectangle at the bottom left of submitted plans. This ensures sufficient clearance for BOTH Miami-Dade County and Doral stamps to be legible.
- Applications may be notarized using a Remote Online Notary and an electronic signature. Scanned, wet-seal notarized signatures are accepted.
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- PV Breaker,Load Side Taps,Meter Adapter,Line Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
#NFZ_ALL#
For Corrections/Revisions:* Only submit the corrected pages for the revision along with a cover page explaining what changes we are making to the plans. Construction Engineering must complete Solar Roof Top PV Building-Structural Requirement and HVHZ Electronic Solar Permit Form See attached files.
ATTACH SIF (SEE FILES)
- Cover Page Notes
All Jobs [THIS SYSTEM DESIGNED WITH:
WIND SPEED: 175
WIND EXPOSURE: C
CATEGORY II
3 SECOND GUST]
- Site Notes
All Jobs [THIS SYSTEM DESIGNED WITH:
WIND SPEED: 175
WIND EXPOSURE: C
CATEGORY II
3 SECOND GUST]
- Attachment Detail
Portrait orientation only Add 'M1 NOA' text to all roof mounted comp shingle projects. Add 'GAF NOA ' text to all roof mounted tile projects.
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim