County of Duval / City of Jacksonville (FL)

Florida Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2020
Fire Code Version2018 Building Code
Wet Stamps RequiredDigital Structural,Digital Electrical
Fire Setback Enforced0

Codes

NEC Code Version
2020
Fire Code Version
2018 Building Code
Code List

2023 8TH EDITION FLORIDA BUILDING CODE: BUILDING

2023 8TH EDITION FLORIDA BUILDING CODE: RESIDENTIAL

2023 8TH EDITION FLORIDA BUILDING CODE: MECHANICAL

2023 8TH EDITION FLORIDA BUILDING CODE: PLUMBING

2023 8TH EDITION FLORIDA BUILDING CODE: FUEL GAS

2023 8TH EDITION FLORIDA BUILDING CODE: ENERGY CONSERVATION

2023 8TH EDITION FLORIDA BUILDING CODE: EXISTING BUILDING

2023 8TH EDITION FLORIDA BUILDING CODE: ACCESSIBILITY

2023 8TH EDITION FLORIDA FIRE PREVENTION CODE (NFPA)

2020 NATIONAL ELECTRIC CODE (NEC)

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

How Many Plansets Required
Other (See Submission Notes)
Revision Required
1
Rough Inspection
None
New Planset Required For Module Swap
0

Stamps

Ee Stamp Required On SLD
Yes
Wet Stamps Required
Digital Structural,Digital Electrical
Structural Calculations Required
Yes
Ee Stamp Notes

FL Statute Letter Required

Digitally Verified Signature

Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
0
Setback Notes

Standard

Structural & loads

Wind Speed
135
Wind Notes

Enter address for wind speed:

https://hazards.atcouncil.org/

Snow Load
0
Reducible Snow Load Allowed
1
Max Attachment Spacing
48
Structural Notes

Digitally Verified Signature

Minimum Ground On Roof
#10

Electrical

Electrical Load Calcs Required
Derates
Allowed POI
PV Breaker,Line Side Taps,Load Side Taps
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
0.91

Battery / ESS

Unique Battery Placards Needed
1
ESS Notes
  • DISCONNECT BETWEEN UM AND MID REQUIRED
  • EACH generating and/or energy storage system (ESS) must have its own manual AC disconnect switch. The disconnect for the battery must be placed next to the battery. Disconnect(s) for the generation system(s) must be placed within 5 feet of the JEA meter and be capable of being locked in the open position with a JEA padlock.
  • If multiple generating systems and/or energy storage systems exist behind the JEA revenue meter, one external AC isolation device must be installed for each to disconnect all generating equipment interconnected with that service.
  • If any of the required disconnect switches cannot be located within 5 feet of the meter, the customer must provide a sign and permanently mount it next to the meter clearly stating location(s) of the switch(es).
  • Disconnect switches must be in visible locations, and accessible to JEA personnel at all times.
  • Site Plan must show the location of the generating system, JEA meter, inverter and all disconnect switches including battery disconnect.
  • Production Meter not required.

AHJ follows NFPA 855 which restricts battery locations to the following:

  • Attached garages
  • Detached garages
  • On exterior walls at least 3 ft (914 mm) way from doors or windows.
  • Outdoors at least 3 ft (914 mm) way from doors or windows.
  • Utility closets
  • Storage or utility spaces
Separate ESS Disconnect Required
Local Disconnect
ESS Elevation Detail Required
No

Plan set

Electrical Diagram

TAPS

  • PIERCING TAPS NOT ALLOWED
  • UTILIZE POLARIS LUGS
  • Utilize tap box for LST
Label Page

FLORDIA 2020 CAD BLOCK

Custom Placards Required
1
Placards Notes

CUSTOM PLACARD 6 X 6 RED w/White Lettering

Non Standard Revision Requirements

ONLY PROVIDE REVISED PAGES WITH A RESPONSE LETTER AND DELTA NUMBER

Ground mount

Ground Mount Fencing Required
Mesh/Scrim
Ground Mount Notes

Setback requirements vary by zone. Call  or

e-mail 

GM max height 15'. Anything higher needs approval from Zoning. 

Ground screws allowed with engineer stamp. 

There are no base material requirements.

All wiring and equipment shall be at or above the Design Flood Elevation.

Septic documentation can be gathered at Florida Department of Health 

Compiled from public records, 2026. Requirements change with code cycles and local amendments. Verify with the County of Duval / City of Jacksonville (FL) building department before you rely on this, and treat it as a research head start, not a ruling. Getting quotes? Run them through the quote checker first.