County of St. Charles (MO)
NEC Code Version2020
Fire Code Version2018 Building Code
Wet Stamps RequiredDigital Structural,Digital Electrical
Fire Setback Enforced1
Codes
- NEC Code Version
- 2020
- Fire Code Version
- 2018 Building Code
- Code List
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL RESIDENTIAL CODE
2021 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2021 INTERNATIONAL FUEL GAS CODE
2021 INTERNATIONAL MECHANICAL CODE
2021 INTERNATIONAL PLUMBING CODE
2020 NATIONAL ELECTRICAL CODE
- IEBC Accepted
- 1
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- 0
- Rough Inspection
- None
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- Yes
- Wet Stamps Required
- Digital Structural,Digital Electrical
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
Structural & loads
- Wind Speed
- 115
- Snow Load
- 20
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- Required - SEALED PLANS REQUIRED: Solar photovoltaic plans both structural and electrical pages must be signed, dated and sealed by a MO professional engineer. Please resubmit plans with either all pages individually sealed or the cover sheet referencing all pages sealed.
- Required - SEALED PLANS REQUIRED: Solar panels installed on an existing structure need to have the structure examined by a professional engineer and a signed and sealed structural analysis reported provided. The cover page listing all pages or all separate pages with details of the project must be signed and sealed by a MO professional engineer.
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Load Side Taps,Line Side Taps,Meter Adapter,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- Separate ESS Disconnect Required
- No
- ESS Elevation Detail Required
- No
Plan set
- Label Page
Please make sure placard on label page reflect 2014 stickers
- Custom Placards Required
- 1
- Placards Notes
Site map placard required.
Ground mount
- Ground Mount Fencing Required
- No
- Setback Front Yard
- 10
- Setback Back Yard
- 5
- Setback Side Yard
- 5