Township of Neptune (Monmouth County) (NJ)
Codes
- NEC Code Version
- 2020
- Fire Code Version
- 2018 Building Code
- Code List
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL RESIDENTIAL CODE
2021 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2021 INTERNATIONAL FUEL GAS CODE
2021 INTERNATIONAL MECHANICAL CODE
2021 INTERNATIONAL PLUMBING CODE
2020 NATIONAL ELECTRICAL CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 4
- Revision Required
- 0
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Wet Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 120
- Wind Notes
Exposure Category B
- Snow Load
- 20
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
**Raised seal required on (4) plans.** SE raised seal wet sign on corresponding PV pages & PE Letter / Calcs. WS:120mph. Exposure B. SL: 20psf Mail 4 sets on 11x17. 201 Commerce Dr Ste. 5 Moorestown, NJ 08057
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Line Side Taps,PV Breaker,Meter Adapter,Load Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 1
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
Zoning officer requires that the page in the planset showing mounting details show that the distance from the roof surface to the **TOP** of the solar pane will be **less than** 6 inches. He also requires that this be **DRAWN TO SCALE**. I've been informed by design that drawing the page to scale isn't possible so **for all projects in this AHJ please create an elevation drawing showing a basic front and side view of the house with mods installed. Please be sure it's notated that the TOP of the solar panels will be less than 6 inches from the roof surface.** -KR
- Attachment Detail
5/27/21 - Update - in conversation with design it's been determined that the required page cannot be drawn to scale. To satisfy AHJ requirements, please create an elevation drawing of the house with solar panels. Drawing must have note stating that the TOP of the solar panels will be less than 6 inches off the roof surface. -KR Must show distance from roof to top of panel (6'' max) -DB * **AHJ requires that drawing showing distance from roof to top of panel is DRAWN TO SCALE -KR** ** ** **IF THE PROPOSED SOLAR PANELS PROJECT MORE THAN 6 INCHES, THEN PLEASE PROVIDE A BUILDING ELEVATION, DISPLAYING THE NEW BUILDING HEIGHT. -KR**
- Electrical Diagram
If lineside tap (LST), then a Hoffman Tap Box (junction box) is required.
- Electrical Diagram Notes
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim