City of Roswell (NM)
NEC Code Version2020
Fire Code Version2015 Building Code
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1
Codes
- NEC Code Version
- 2020
- Fire Code Version
- 2015 Building Code
- Code List
2018 INTERNATIONAL BUILDING CODE 2018 INTERNATIONAL RESIDENTIAL CODE 2018 INTERNATIONAL FIRE CODE 2018 INTERNATIONAL ENERGY CONSERVATION CODE 2018 INTERNATIONAL EXISTING BUILDING CODE 2018 INTERNATIONAL FUEL GAS CODE 2018 INTERNATIONAL MECHANICAL CODE 2018 INTERNATIONAL PLUMBING CODE 2020 NATIONAL ELECTRICAL CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 1
- Revision Required
- 1
- Rough Inspection
- Rough Electrical
- New Planset Required For Module Swap
- 1
Stamps
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Ridge Setback
- 36
- Hip Valley Setback
- 18
- Setback Notes
AHJ wants 18" on both sides of ALL FLAT VALLEYs. Not only where the porch meets the roof, but where ANY Low Slope Roof Meets the Pitched Roof (including additions, covered patios etc)
Structural & loads
- Wind Speed
- 115
- Wind Notes
Exposure Category B
- Snow Load
- 5
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Standard
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- All Jobs
- Allowed POI
- Load Side Taps,PV Breaker,Meter Adapter,Line Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
- Attachment Detail Notes
Cannot use the rocket systems due to bonding being though panels.
- Electrical Diagram
- AHJ wants #8 EGC (Ground) from inverter to POI
- AHJ wants #6 AWG wire from the inverter to POI
- From modules to inverter on line diagram add "OR METAL FLEX CONDUIT" after EMT.
***EXAMPLE: #8 EGC, THWN-2 IN 3/4' OR LARGER EMT OR METAL FLEX CONDUIT". (New update from AHJ 12/17/2024)***
- Placards Notes
- if the electrical equipment is not accessible ( Example: fence back yard ) Site map is needed on the wall by the electrical equipment Pending additional information.
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim