City of Central Point (OR)
Codes
- NEC Code Version
- 2023
- Code List
2022 OREGON STRUCTURAL SPECIALTY CODE
2023 OREGON RESIDENTIAL SPECIALTY CODE
2023 OREGON PLUMBING SPECIALTY CODE
2023 OREGON ELECTRICAL SPECIALTY CODE
2025 OREGON ENERGY EFFICIENCY SPECIALTY CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- 1
- New Planset Required For Module Swap
- 1
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Pathways must be over supported areas of the roof; pathways cannot include roof overhang.
Structural & loads
- Wind Speed
- 96
- Snow Load
- 25
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 48
- Minimum Ground On Roof
- #10
Electrical
- Allowed POI
- Load Side Taps,Meter Adapter,PV Breaker,Line Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
ESS disconnect required within 6ft of MSP on same wall and not blocked by walls/gates/etc
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- Yes - with dimensions
Plan set
- Plan Set Requirements
AHJ Requirements - Structural
any manufactured homes(with2x2 truss), flat roof, tiled roofs, metal framing, or pole buildings we cannot apply prescriptively. These all require Structural Stamps, PE Letter, and Calcs
Please obtain the following when designing on any manufactured homes(with2x2 truss), flat roof, tiled roofs, metal framing, or pole buildings
-Stamps on plans
-PE Letter
-structural calcs
- Attachment Detail
Attachments shall be spaced not greater than 24 inches (609.6 mm) on center in any direction where: * Ground snow loads (https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#loads_455.715_definitions_for_ors_455.715_to_455.740) exceed 36 psf (1.197 kN/m2). * Located within 3 feet (914 mm) of a roof edge, hip, eave or ridge. * Located in wind Exposure Category B or greater and the _wind speed_ exceeds 120 mph. * Located in wind Exposure Category C or greater and the _wind speed_ exceeds 110 mph.
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim