City of Gearhart (OR)
NEC Code Version2023
Fire Code Version2018 Building Code
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2021 OREGON RESIDENTIAL SPECIALTY CODE
2021 OREGON ELECTRICAL SPECIALTY CODE
2023 OREGON ELECTRICAL SPECIALTY CODE
2025 OREGON ENERGY EFFICIENCY SPECIALTY CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- 1
- New Planset Required For Module Swap
- 1
Fire setbacks
- Setback Notes
- Standard
Structural & loads
- Wind Speed
- 999
- Snow Load
- 999
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 48
- Minimum Ground On Roof
- #10
Electrical
- Allowed POI
- Meter Adapter,Line Side Taps,PV Breaker,Load Side Taps
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
- Standard
Plan set
- Plan Set Requirements
Complete the "OR PV Checklist" from the files below to determine if PE is required. If we can follow the prescriptive path in the checklist, no PE is needed.
- Attachment Detail
Attachments shall be spaced not greater than 24 inches (609.6 mm) on center in any direction where:
- Ground snow exceed 36 psf (1.197 kN/m2).
- Located within 3 feet (914 mm) of a roof edge, hip, eave or ridge.
- Located in wind Exposure Category B or greater and the wind speed exceeds 120 mph.
- Located in wind Exposure Category C or greater and the wind speed exceeds 110 mph.
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim