City of Woodburn (OR)
Codes
- NEC Code Version
- 2023
- Code List
2021 OREGON STRUCTURAL SPECIALTY CODE
2021 OREGON RESIDENTIAL SPECIALTY CODE
2025 OREGON ENERGY EFFICIENCY SPECIALTY CODE
2023 NATIONAL ELECTRICAL CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- 1
- New Planset Required For Module Swap
- 0
Stamps
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Where the array does not exceed 25 percent of total roof area, a minimum 12" unobstructed pathway shall be maintained along each side of any horizontal ridge.
We will also need to label at least 1 fire pathway of 36" down the side of the home, any part of the roof that overhangs the building cannot be counted in this 36" pathway.
Fire pathways cannot be within 12" from the low point of a valley.
Structural & loads
- Wind Speed
- 999
- Snow Load
- 999
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 48
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Load Side Taps,Line Side Taps,Meter Adapter,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
Please provide a sketch or picture of existing rafter bracing such as collar ties, purlins, knee walls, or doubled rafters. If none exist, please choose one of the methods to install only in affected areas.
- Roof Plan
Provide a sketch or photo of existing rafter bracing such as collar ties, purlins, knee walls, or doubled rafters. If none exist, please choose a method to apply only in affected areas.
- Attachment Detail
Attachments shall be spaced not greater than 24 inches (609.6 mm) on center in any direction where:
- Ground snow exceed 36 psf (1.197 kN/m2).
- Located within 3 feet (914 mm) of a roof edge, hip, eave or ridge.
- Located in wind Exposure Category B or greater and the _wind speed_ exceeds 120 mph.
- Located in wind Exposure Category C or greater and the _wind speed_ exceeds 110 mph.
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim