County of Klamath (OR)
Codes
- NEC Code Version
- 2023
- Code List
2021 OREGON RESIDENTIAL SPECIALTY CODE
2019 OREGON STRUCTURAL SPECIALTY CODE
2019 OREGON MECHANICAL SPECIALTY CODE
2021 OREGON PLUMBING SPECIALTY CODE
2023 OREGON ELECTRICAL SPECIALTY CODE
2025 OREGON ENERGY EFFICIENCY SPECIALTY CODE
2019 OREGON ZERO ENERGY READY COMMERCIAL CODE
2019 OREGON FIRE CODE
2010 OREGON MANUFACTURED DWELLING INSTALLATION SPECIALTY CODE
- IEBC Accepted
- 1
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- 0
- Rough Inspection
- None
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Klamath requires 2018 Oregon fire setback codes:
- Solar panel systems must have a 36-inch-wide clear pathway on three sides of the solar roof.
- Pathways cannot be located along the bottom edge of roofs with a slope steeper than 2:12.
- All required pathways must be over structurally supported areas (from the load-bearing wall inward) and measured from the roof edge or ridge to the solar array.
Exceptions:
- Small solar systems (≤1,000 sq ft) on sloped roofs (over 2:12):
- If the solar array covers 25% or less of the total roof area: provide a 12-inch clear pathway along both sides of the ridge.
- If the solar array covers more than 25%: provide a 36-inch ridge-to-eave path plus the 12-inch ridge-side paths.
- Non-occupied accessory structures don’t need pathways if they are at least 6 feet away from occupied structures or separated by a 2-hour fire-rated wall.
- Townhouses with proper fire separation can be treated as a single structure and follow the same small solar system exception rules.
Structural & loads
- Wind Speed
- 100
- Wind Notes
Wind speed is 98 MPH
- Snow Load
- 20
- Snow Load Notes
20 lbs Roof snow load non reducible.
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 48
- Structural Notes
View the requirements for the prescriptive path in the plan notes below. If all requirements are met, engineering is not required.
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- PV Breaker,Line Side Taps,Load Side Taps,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Attachment Detail
Roof mounted installations on Risk Category I or Risk Category II on structures of conventional light-frame construction that comply with this section shall qualify as prescriptive and shall not require an engineered design if all of the following criteria are met:
(https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#conventional_light-frame_construction)
1. The ground snow load does not exceed 50 psf, wind speeds do not exceed 120 mph for Exposure Category C or 135 mph for Exposure Category B with pre-engineered trusses or rafters spaced at 24 inches (610 mm) on center maximum.
Existing rafter spans shall comply with Section 2308.7.2 (https://up.codes/viewer/oregon/ibc-2018/chapter/23/wood#2308.7.2).
Where the existing grade and species cannot be verified, it is assumed to be #2 staff-Larch
(https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#grade_lumber)
**EXCEPTION**
PV installed on roofs of detached one and two family dwellings and occupancies where the existing supporting roof framing is conventional light-frame construction with pre-engineered trusses or rafters spaced at 24 inches (610 mm) on center maximum, the ground snow load does not exceed 70 psf, and the site is limited to wind Exposure Category B or C.
(https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#dwelling)_ and _[townhouses]
(https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#townhouse)_ classified as Group R-3 (https://up.codes/viewer/oregon/ibc-2018/chapter/3/occupancy-classification-and-use#310.4) and [Group U]
(https://up.codes/viewer/oregon/ibc-2018/chapter/3/occupancy-classification-and-use#312)
Existing rafter spans shall comply with Section R802.5
(https://up.codes/viewer/oregon/irc-2018/chapter/8/roof-ceiling-construction#R802.5) of the _Residential Code_.
2. Roofing material shall be metal, single-layer wood shingle or shake, or not more than two layers of composition shingle.
3. The combined weight of the photovoltaic modules shall not exceed 4.5 pounds per square foot (2.0412 kPa).
Photovoltaic modules shall be directly attached to the roof framing or blocking.
Attachments must be spaced not greater than 48 inches (1219 mm) on center in any direction.
UNLESS
1. 3.1. Ground snow loads exceed 36 psf (1.197 kN/m2).
2. 3.2. Located within 3 feet (914 mm) of a roof edge, hip, eave or ridge.
3. 3.3. Located in wind Exposure Category B or greater and the wind speed exceeds 120 mph.
4. 3.4. Located in wind Exposure Category C or greater and the wind speed exceeds 110 mph.
THEN
Attachments shall be spaced not greater than 24 inches (609.6 mm) on center in any direction where:
**Exception**
Photovoltaic modules may be attached directly to standing seam metal using clamps and roofing materials that meet the following criteria:
1. The allowable uplift capacity of clamps shall be not less than 115 pounds for clamps spaced at 60 inches (1525 mm) on center or less as measured along the seam or not less than 75 pounds for clamps spaced at less than 48 inches (1219 mm) on center.
2. Clamp spacing perpendicular to seams shall not exceed 24 inches (610 mm). Spacing of clamps along a seam shall not exceed 60 inches (1525 mm).
3. Roofing panels shall comply with all of the following:
1. 3.1. Shall be a minimum of 26 gage steel,
2. 3.2. Shall be a maximum of 18 inches (457 mm) in width,
3. 3.3. Shall be attached with a minimum of #10 screws at 24 inches (610 mm) on center,
4. 3.4. Shall be installed over minimum 1/2-inch (12.7 mm) attached to framing with 8d nails at 6 inches (153 mm) on center at roof panel edges and 12 inches (305 mm) on center field nailing
(https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#nominal) wood structural panels (https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#wood_structural_panel) (https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#panel_part_of_a_structure) (https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#nailing_field).
4. **Height** : Module height above roof shall not exceed 18 inches (457 mm) from the top of the module to the roof surface and shall be in accordance with Figures 3111.3.5.3(1) and 3111.3.5.3(2).
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- No
- Ground Mount Notes
Setbacks are determined by the zoning for the property and the height of the structure. If the array will be less than 14’ high the rear and side setbacks can be no less than 5’, if the array is taller standard setbacks will apply. See Document "Ground Mount Heights and Setbacks" in the files section See Document "Ground Mount Site Plan Example" in the files section Setback info: Jenny MacKrell is the Permit Tech in the On-Site/Septic Department. She can be reached via email, or by