City of Wichita Falls (TX)
Codes
- NEC Code Version
- 2020
- Fire Code Version
- 2018 Building Code
- Code List
2015 INTERNATIONAL RESIDENTIAL CODE
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL EXISTING BUILDING CODE
2015 INTERNATIONAL PLUMBING CODE
2015 INTERNATIONAL MECHANICAL CODE
2015 INTERNATIONAL FUEL GAS CODE
2015 INTERNATIONAL FIRE CODE
2006 INTERNATIONAL ENERGY CODE
2020 NATIONAL ELECTRIC CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- 1
- Rough Inspection
- Rough Electrical
- New Planset Required For Module Swap
- 1
Stamps
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
## 2015 IFC: _ **Hip Roof layouts**_ : 3 ft wide clear access pathway from the eave to the ridge on each roof slope where the panels and modules are located. _ **Single Ridge Roofs**_ : 3 ft wide access pathways from the eave to the ride on each roof slopes where panels and modules are located. _ **Roof with Hips and Valleys:** _18 inches to a hip or valley where panels/modules are to be placed on both sides of a hip or valley that is of equal length, the panels shall be permitted to be placed directly adjacent to the hip or valley.
Structural & loads
- Wind Speed
- 115
- Wind Notes
Exposure Category B
- Snow Load
- 5
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Flatten Plans PDF / Remove Layers prior to sending to engineer for stamps. SE digital stamps on corresponding PV pages, PE Letter & Calcs. WS: 115MPH, Exposure Cat. B, GSL: 5LBS
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- PV Breaker,Load Side Taps,Line Side Taps,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
2015 IFC: Each photovoltaic array shall be limited to 150 ft by 150 ft. Multiple arrays shall be separated by a 3ft wide clear access pathway. Hip Roof layouts: 3 ft wide clear access pathway from the eave to the ridge on each roof slope where the panels and modules are located. Single Ridge Roofs: 3 ft wide access pathways from the eave to the ride on each roof slopes where panels and modules are located. Roof with Hips and Valleys: 18 inches to a hip or valley where panels/modules are to be placed on both sides of a hip or valley that is of equal length, the panels shall be permitted to be placed directly adjacent to the hip or valley. Flatten PDF plans / remove layers before sending to PE for stamps.
- Attachment Detail
Each photovoltaic array shall be limited to 150 ft by 150 ft. Multiple arrays shall be separated by a 3ft wide clear access pathway.
- Electrical Diagram
When adding a new Meter Can it must have a metallic bond from PVC riser to the can
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim