City of Aberdeen (WA)
Spot something wrong?
These change with code cycles. If a requirement here is out of date or missing, tell us and we'll fix it.
Report a correctionCodes
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- No
- New Planset Required For Module Swap
- No
Structural & loads
- Reducible Snow Load Allowed
- Yes
Electrical
- Allowed POI
- PV Breaker,Line Side Taps,Meter Adapter,Load Side Taps
- Supply Tap Neutral Ground Bond Required
- Yes
Plan set
- Electrical Diagram
For all Line Side Connections:
- Neutral and ground bonded in fused disconnect
- #6 bare copper run from N/G bar to (E) MSP's GEC and crimped
- Schedule 80 PVC must be used in between fused disconnect and MSP - only showing 2 hots and neutral
- All other conduit can be EMT
For all Load Side Taps:
- Schedule 80 PVC must be used in between disconnect and MSP