Tacoma Public Utilities (WA)

Washington Authority Having Jurisdiction Solar permitting requirements

Codes

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

Revision Required
1
New Planset Required For Module Swap
0

Structural & loads

Reducible Snow Load Allowed
1

Electrical

Allowed POI
PV Breaker,Load Side Taps,Line Side Taps,Meter Adapter
Supply Tap Neutral Ground Bond Required
1

Plan set

Electrical Diagram

For all Line Side Connections:

  • Neutral and ground bonded in fused disconnect
  • #6 bare copper run from N/G bar to (E) MSP's GEC and crimped
  • Schedule 80 PVC must be used in between fused disconnect and MSP - only showing 2 hots and neutral
  • All other conduit can be EMT

For all Load Side Taps:

  • Schedule 80 PVC must be used in between disconnect and MSP
Custom Placards Required
0