City of Roseville California
Net metering & export
- Rebates Offered
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 1
- Supply Side Taps Allowed
- 0
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- Percentage
- Offset Value
- 100
- Offset Calculation Basis
- Historical
- Offset Calculation Period
- 12
- Industry Standard Watts Sqft
- 3
- System Offset Notes
- Customer-Generators may install systems no larger than 100% of the last 12 months of energy use recorded by the electric meter.
- Residents with less than 12 months of energy use may use 3 kWh per square foot as the maximum allowed using the Developed Building square footage from the on-line Property Report. https://roseville.maps.arcgis.com/apps/webappviewer/index.html?id=2a67e5a4e1cc4f489868b6563589bf19
- Offset Calc Tool
- CSI
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- Meter Spot Process
See Files attachment "Residential Electric Service Upgrade"
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
Battery Jobs:
- Roseville Electric requires an AC disconnect for each interconnected source.
- The AC disconnect must be within sight of the main electric panel, within 5' of the main electric panel, and have a visible open disconnect device
- Provide load calculations for the backup load center (and ensure all appliance/equipment with wattages are indicated)
- Electric Service Reqs
SOLAR READY MPU's NOT ALLOWED PER UTILITY
- Install Reqs
## SOLAR READY MPU's NOT ALLOWED PER UTILITY
Projects installed without interconnection approval are subject to being fined, and may be locked off until the required documentation is submitted and the Approval to Interconnect (Form D) is signed by Roseville Electric Utility.
- Website
- link
- Phone
- (916) 797-6937
Other details
- Restrict Inspection
- 0
- Address ID
- 108054
- Express Planset Eligible
- Yes