TID - Turlock Irrigation District
Spot something wrong?
Tariffs and interconnection rules move often. If something here is out of date or missing, tell us and we'll fix it.
Report a correction Net Metering AllowedYes
Supply Side Taps AllowedNo
Line Taps AllowedNo
Load Taps AllowedNo
AC Disconnect RequiredYes
Net metering & export
- Net Metering Allowed
- Yes
- TOU Utility
- Yes
- Post Solar Billing Method
- Net Metering
- Solar Export Type
- N/A
- Rebates Offered
- No
- Deregulated
- No
Interconnection & taps
- Approval Req To Install
- Yes
- Supply Side Taps Allowed
- No
- Line Taps Allowed
- No
- Load Taps Allowed
- No
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- No
- System Size Includes Existing Systems
- No
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- Offset Calc Tool
- EPBB
Metering & disconnect
- Production Meter Required
- Situational
- Production Meter Criteria
- Production meter is optional, but if installed needs to be within sight of MSP. (do not put on plans unless requested
- Production Meter Position
- Inv-PM-Disco-POI
- Production Meter Labeling
- Production Meter
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Utility AC Disconnect
- Meter Spot Required
- Yes
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
- We can use an AC or DC disconnect. If using a DC disconnect, Label as EXTERNAL, LOCKABLE KNIFE BLADE DC DISCONNECT SWITCH
- Must not exceed the 120% rule. Utility is strict.
Existing Systems
- If a production meter exists, both systems go through one production meter
- Electric Service Reqs
Standard
- Placards
- Rapid Shutdown Placards need to be red.
- Please.
- MSP: WARNING: EQUIPMENT FED BY MULTIPLE SOURCES, TOTAL RATING OF ALL OVERCURRENT DEVICES EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR
- Electrical Stamp Required
- No
- Meter Num Req SLD 3LD
- No
- ESID Num Req SLD 3LD
- No
- Electrical Diagram Notes
All Jobs [LOCKABLE KNIFE BLADE AC DISCONNECT SWITCH WITH VISIBLE OPEN. MUST BE ACCESSIBLE, WITHIN 10' OF, AND WITHIN SIGHT OF, MSP. MUST BE MARKED PER NEC 690.14.C.2 AND 690.52]
- Rate Schedule Link
- link
- Website
- link
- Phone
- 209-883-8301
Other details
- Revision Required
- Yes
- Mod Swap Requires Planset
- Yes