SECPA - Southeast Colorado Power
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Annual
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Net Excess Generation Notes
Excess generation is banked and carried forward month to month and applied on a one-to-one basis. After the February Billing and before the March billing of each calendar year, any remaining unused balance of accrued kWh shall be credited to the customer at the Tri-State Generation and Transmission current wholesale rate.
- Rebates Offered
- 0
- Deregulated
- 0
- Allows Standby
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Offset Notes
10 kW for residential
25kW for commercial
Alternative Sizing Not Allowed
Metering & disconnect
- Allowed Meter Adapter
- None
Plans & docs
- Site Plan Reqs
Show UM on the site plan.
- SLD Reqs
Production Meter is required. Any standard 2S meter socket is approved.
- Electric Service Reqs
If an inverter system is to operate during the loss of utility voltage, equipment designed for this type of operation (islanding) must be installed. An Automatic Transfer Switch to disconnect the utility source during islanded operation will be required. Inverters designed with separate outputs for grid-tie and off-grid operation will also be required.
- Install Reqs
We install the socket, utility will provide and install the meter
- Placards
A permanent and weatherproof sign indicating the location of the QF Generation Disconnect shall be clearly displayed at the point of service connection (generally at the customer meter). For QFs greater than 10 kW of capacity, a one-line electrical diagram and the names and current telephone numbers of at least two persons authorized to provide access to the QF, and who have authority to make decisions regarding the QF interconnection and operation, shall be included with or attached to the sign. This telephone listing shall be updated as needed to maintain its usefulness.
- Rate Schedule Link
- link
- Website
- link
Other details
- Restrict Inspection
- 0
- Address ID
- 254107
- Express Planset Eligible
- Yes