GRU - Gainesville Regional Utilities
Spot something wrong?
Tariffs and interconnection rules move often. If something here is out of date or missing, tell us and we'll fix it.
Report a correctionNet metering & export
- Net Metering Allowed
- Yes
- NEM Type
- Annual
- TOU Utility
- No
- Post Solar Billing Method
- Net Metering
- Solar Export Type
- Avoided Cost
- Net Excess Generation Notes
Owner/Operator shall receive a monthly energy credit for all excess kilowatt-hours delivered into the distribution system. If the energy credit exceeds the total electric energy billed amount in any corresponding month, the excess energy credit shall be applied to the subsequent month’s billing. An annual true up with conversion to money will be applied at the end of each calendar year using an avoided cost price. GRU reserves the right to develop the annual avoided cost pricing and/or modify its tariff at any time without prior notice to Owner/Operator.
- Rebates Offered
- No
- Allows Standby
- Yes
Interconnection & taps
- Approval Req To Install
- Yes
- Supply Side Taps Allowed
- No
- Line Taps Allowed
- No
- Load Taps Allowed
- No
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- No
- System Size Includes Existing Systems
- No
- Offset Type
- Percentage
- Offset Value
- 100
- Offset Calculation Basis
- Historical
- Offset Calculation Period
- 12
- Industry Standard Watts Sqft
- 2
- Offset Calc Tool
- Historical Usage
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- AC Disconnect Required
- Yes
- Allowed Meter Adapter
- None
Plans & docs
- Site Plan Reqs
PROVIDE INTERSECTING ROAD
- SLD Reqs
ELEVATION DRAWING REQUIRED ON ALL PROJECTS
- Electric Service Reqs
System Sizing
- The generation will be considered to be oversized if the kW DC rating of the PV generation is more than the average annual single account, on-site consumption (kWh) divided by 1393. (Note: Approximately 1 kW DC of PV generation will produce approximately 1393 kWh AC per year.)
3 Phase
- The output of the PV system shall be balanced between the three phases when interconnecting to a 3 phase transformer. The PV output shall be balanced so that the difference in current (amperes) between phases shall be 10% or less, as measured from the most heavily loaded phase to the least loaded phase. Single phase connection to a three phase transformer will not be allowed.
Taps
- NO TAPS IN METER
- Install Reqs
- Placards
Examples of Placards. See page 100 of the Energy Delivery Service Guide.
GRU Placard requirements should be referenced on design drawings.
Placards shall be red with white block lettering.
Inverter
- Installations that have instrument-rated metering shall require additional labeling as directed by qualified GRU personnel. A few examples would be (1) a label indicating the AC disconnect location (2) the CT’s polarity mark should point toward the inverter (which is the source), etc.
Revenue Socket (Utility Meter)
- The placards shall be permanently riveted to the covers, and shall be made of red, weatherproof, hard plastic, with engraved white block lettering
GRU revenue meter socket cover
- Clearly labeled “Warning: Electric Shock Hazard. The terminals on both line and load side may be energized in the open position” readily visible to GRU personnel.
AC Disconnect
- The placard shall be permanently riveted to the disconnect device, and shall be made of red, weatherproof, hard plastic, with engraved white block lettering. Must be clearly labeled “Auxiliary Generation Disconnect” and be readily visible to GRU personnel.
Site Placard
- Electrical Diagram Notes
All Jobs [AC DISCONNECT TO BE WITHIN 10FT OF MAIN DISCONNECTING MEANS OF HOME // PLACARDS SHALL BE RED WITH WHITE BLOCK LETTERING. GRU REQUIRES PLACARDS WITH THE STANDARD REQUIRED VERBIAGE ON AC DISCONNECT AND REVENUE METER RESPECTIVELY]
- Rate Schedule Link
- link
- Website
- link
- Phone
- (352) 393-1460
Other details
- Revision Required
- No
- Mod Swap Requires Planset
- Yes