Ameren Illinois
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Monthly
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Solar Export Type
- N/A
- Net Excess Generation Notes
For applications after January 1, 2025, excess generation will be credited to the bill's Supply section. These credits will not expire and will carry over until they are used. When applying for net metering, the applicant will need to choose between two methods:
- kWh Yes - (kWh Usage Netting): On-site excess generation (including prior carryover kWh) will net from Total kWh in calculating Supply Net Total kWh and Supply Net Billable kWh while the Delivery Net Billable kWh will equal Total kWh.
- kWh No - (Monetary Value Netting): This method coverts your excess generation into monetary credits based on current pricing. Excess Monetary credits are carried over to the next bill to be applied to the supply section.
- Rebates Offered
- 1
- Deregulated
- 1
- Allows Standby
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 2
- Supply Side Taps Allowed
- 1
- Line Taps Allowed
- 1
- Load Taps Allowed
- 1
- Tap Criteria
- NO LST IN UTILITY OWNED EQUIPMENT
- Insulation -piercing connectors are NOT permitted
- No tap boxes
- Remove ground from disconnect to POI for line side tap. provide bonding jumper in disconnect
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Size Justification
- Load Justification
- Offset Calc Tool
- Utility Tool
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- AC Disconnect Required
- Yes
- Meter Spot Required
- 0
- Allowed Meter Adapter
- Tesla Backup Switch
Plans & docs
- Site Plan Reqs
- Include full name, including initials if required
AC Disconnect:
- Must be NEMA 3R outdoor rated and mounted near utility meter.
- SLD Reqs
All Projects
AC Disconnect
- Electrically, the switch should be located between the output of the inverter and the Ameren Illinois system. Typically, the switch will be located between the inverter and a circuit breaker or fuse located in the main distribution panel.
- The switch must have a visibly open gap between the switch contacts, knife-blade type. Circuit breakers are NOT suitable for this purpose.
- The switch must be able to be locked in the open position.
- Label AC disconnect as:
- If its PV project: PV AC disconnect , lockable, properly labeled, and accessible 24/7
- if its a PV+ ESS project: PV/ESS AC disconnect , lockable, properly labeled, and accessible 24/7
Battery Projects
- DC Coupled Batteries ONLY. Ameren does not allow AC Coupled batteries (Tesla and SolarEdge are DC coupled, Enphase = AC Coupled)
- DC disconnect between BUI and energy bank.
- AC disconnect between inverter and BUI required.
- Battery Projects with a whole home backup, or Main Panel Insert where we have to cut the conductors, require an MPU with Meter Lever Bypass and a solo main breaker.
- Electric Service Reqs
If intercepting the meter for an MBE/MPI/BUI/Or Gateway, the utility will require a lever bypass meter with main breaker (Escalate to ER if these exist)
- When showing lever bypass meter on the plans show main breaker in the enclosure as well (please size this breaker accordingly to site conditions).
- Example: staff (557489)
- IF PERMITS ARE NOT REQUIRED IN THE AHJ, THE ABOVE WILL NOT BE REQUIRED.
IF USING SUMMATION RULE AS POI WE ARE TO
- Provide clear labeling of all breakers in the MSP on the ELD.
- This does not apply to the 120% rule per email with inspector
- Placards
- Electrical Stamp Required
- 0
- Meter Num Req SLD 3LD
- 1
- ESID Num Req SLD 3LD
- 0
- Site Plan Notes
- Label Page Notes
- Cover Page Notes
- Electrical Diagram Notes
LST [Line Side Tap suitable for use on the line side of service equipment.]
All Jobs [The PV/ESS AC disconnect is within 10 feet of the utility meter and is lockable, labeled, and accessible 24/7.]
Battery [PV RAPID SHUT DOWN COMPLIES WITH ASM 1500.01(6), ASM 1500.02(6), AND ASM 1500.01(8) // UTILITY METER WILL BE REPLACED TO NEW LEVER BYPASS METER]
- Rate Schedule Link
- link
- Website
- link
- Phone
- (800) 755-5000