Eversource Energy (Western MA)
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Monthly
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Net Excess Generation Notes
Excess generation at the end of each month is credited at the applicable retail electricity rate and rolled forward to future bills as a dollar credit. This credit rolls forward indefinitely to future bills but cannot be "cashed out".
- Rebates Offered
- 1
- Deregulated
- 1
- Allows Standby
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Supply Side Taps Allowed
- 1
- Line Taps Allowed
- 1
- Load Taps Allowed
- 1
- Tap Criteria
- LST does not require 2 disconnects as long as Fused Disco is accessible outside.
- Automatic Transformer Upgrade Size
- 20
- Automatic Transformer Upgrade Size Type
- kW AC
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- Utility Specific Adjustments
- Please try to be <15KW AC system size whenever possible. For example: Please use mix of 7.6KVA and 5.7KVA to be under 15KW AC rather than using two 7.6KVAs as long as finance inverter OD ratio is under the limit. This will avoid Level 2 application and reduce approval times. Also avoids EE stamp.
- Eversource Hosting Capacity Map
- System Offset Notes
Metering & disconnect
- Production Meter Required
- Situational
- Production Meter Criteria
Production Meter (SMART meter)
- Required for: Cash, Loan, Aura, Aura+
- Not required for: Lease projects
- Wire inverter on bottom side and utility on top side
- Only 1 production meter per project
- Second meter allowed only if 12 months have passed since existing system PTO
- Production Meter Position
- Inv-Disco-PM-POI
- Production Meter Labeling
- Production Meter
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
- Meter Spot Process
- Before you dig, call them at 1-888-DIG SAFE () to get underground utilities marked. For more info, visit www.digsafe.com.
- Allowed Meter Adapter
- None
Plans & docs
- Site Plan Reqs
- The module: NE SOLAR: NESE370-60MH is not an acceptable module in this utility as it does not meet their safety standards.
- Show parcel boundaries (property/lot lines).
- Show distance from UM to Eversource Transformer in feet. See "Utility Meter to Transformer" in Files section of this page. If proximity requirements cannot be met, request a variance from Eversource. If a variance is granted, placard the UM stating that there is solar generation on site, and show the location of the AC Disconnect.
- Placard the AC Disconnect stating that it is for solar generation.
- Include Peak/Max Output
- SLD Reqs
- Include Peak/Max Output
- Projects over 15 kW AC require an EE stamp
- Electric Service Reqs
- Will require a meter relocation whenever the utility meter is located on the interior, or in any cabinets
- Install Reqs
- Placards
- If AC Disconnect cannot be 24/7 accessible, within 10 feet of, within visible sight of, and on same wall as Utility Meter, request a variance from Eversource. If a variance is granted, placard the UM stating that there is solar generation on site, and show the location of the PM and AC Disconnect. Placard the PM and AC Disconnect stating that they are for solar generation.
- Electrical Stamp Required
- 0
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Site Plan Notes
All Jobs [AC Disconnect shall be 24/7 accessible, within 10 feet of, within visible sight of, and on same wall as Utility Meter // AC Disconnect will be labeled with the location of the Utility Meter. A placard on the Utility Meter will show the location of the Disconnect.]
- Electrical Diagram Notes
All Jobs [AC Disconnect shall be 24/7 accessible, within 10 feet of, within visible sight of, and on same wall as Utility Meter // AC Disconnect will be labeled with the location of the Utility Meter. A placard on the Utility Meter will show the location of the Disconnect.]
- Website
- link
- Phone
- (888) 783-6616
Other details
- Restrict Inspection
- 1
- Revision Required
- 1
- Address ID
- 245164
- Express Planset Eligible
- Yes