PEPCO (MD)
Net metering & export
- Net Metering Allowed
- 1
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Rebates Offered
- 1
- Allows Standby
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Supply Side Taps Allowed
- 1
- Line Taps Allowed
- 1
- Load Taps Allowed
- 1
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 1
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- Percentage
- Offset Value
- 200
- Offset Calculation Basis
- Historical
- Offset Calculation Period
- 12
- Industry Standard Watts Sqft
- 2
- System Offset Notes
Add up the total energy consumption (in kWh) as shown on your last 12 Pepco bills. Divide that sum by 1,200. Multiply that number by 2. The result is the maximum inverter nameplate rating you can install. We use the formula (12-month kWh usage / 1,200) x 2 = maximum kW inverter rating, to comply with state rules, meet all or part of your electrical needs, and follow our regulatory requirements.
The system capacity can be up to 200% of your 12-month historical energy consumption.
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
Inverter must have the label “Smart Inverter or “Smart Inverter Compliant” stamped/written on it. (Effective 10/7/2024 per PEPCO’s new protocol)
- Install Reqs
Any non NEM customer going solar, will be required to have their meter exchanged to an Net Energy Meter.
- Electrical Diagram Notes
All Jobs [AC disconnect is visible, lockable, taggable, and 24/7 utility accessible]
- Website
- link
- Phone
- (866) 634-6977
Other details
- Restrict Inspection
- 0
- Revision Required
- 1
- Mod Swap Requires Planset
- 1
- Express Planset Eligible
- Yes