Xcel Energy (MN)

Minnesota Utility Interconnection & net metering rules
Net Metering Allowed1
NEM TypeMonthly
Line Taps Allowed1
Load Taps Allowed1
AC Disconnect RequiredYes

Net metering & export

Net Metering Allowed
1
NEM Type
Monthly
TOU Utility
0
Post Solar Billing Method
Net Metering
Rebates Offered
0
Deregulated
0
Allows Standby
1

Interconnection & taps

Approval Req To Install
Yes
Interconnection Level
3
Line Taps Allowed
1
Load Taps Allowed
1
Tap Criteria
  • For Load/Line side taps: If system less than 10kW DC = Inv > 60A Fused Disco > POI. The AC disconnect is NOT the utility AC disconnect. Do not include the note. 
  • If system more than 40kW DC = Inv > Non-fused Disco > top of PM > 60A Fused Disco > POI. Non-fused disconnect is the utility AC disconnect. Label and note accordingly.
Automatic Transformer Upgrade Size
0

System size & offset

System Size Restrictions
40
System Size Restriction Type
AC kW
System Size Battery Included
0
System Size Includes Existing Systems
1
Offset Type
No Restrictions
Offset Value
0
Offset Calculation Period
0
Industry Standard Watts Sqft
2
System Offset Notes

40 kW AC max

Systems over 40 kW will have a 120% offset requirement

Metering & disconnect

Production Meter Required
Situational
Production Meter Criteria

 PM is only required on Systems 40kw or larger

Production Meter Position
Inv-Disco-PM-POI
Production Meter Labeling
Production Meter
AC Disconnect Required
Yes
AC Disconnect Labeling
Visible Lockable Labeled Disconnect

Plans & docs

Site Plan Reqs


Approved Planset: Lucky Amedu (461924) ()


Xcel MN Checklist: CHECKLIST


SITE PLAN SHOULD HAVE ALL EQUIPMENT LABELED PROPRERLY SHOWING ELECTICAL PHASING AND VOLTAGE EX: 1-PHASE 240V


CROSS ROAD SHOULD BE SHOWN ON SITE PLAN


Electrical Component Locations

  • SEPERATE BLOCKS FOR UTILITY METER AND MSP SHOULD BE UTILIZED ON SITE PLAN
  • AC DISCONNECT SHOULD BE WITHIN 10FT OF UM, DISTANCE SHOULD BE NOTATED ON TLD
  • PLACARD REQUIRED IF EQUIPMENT IS NOT WITHIN 10FT OF UTILITY METER  
  • OVER HEAD LINES SHOULD HAVE PROPER 3FT CLEARANCE FROM MAST

GROUND MOUNT PROJECTS

  • An access road is required to all Xcel Energy equipment, including production metering and AC disconnects. The width of this road shall be indicated and cannot be less than 12’ wide. It shall show the route from a public road to the Xcel Energy equipment.  Include sufficient space of turn‐ around for ease of accessibility.   
SLD Reqs

All requirements are listed below.

  • AC DISCONNECT SHOULD BE LABELED AS "UTILITY AS DISCONNECT VISIBLE, LOCKABLE, READILY ACCESSIBLE "
  • UTILITY METER PHASE AND VOLTAGE SHOULD BE ADDED TO TLD EX: 1-PHASE, 3 WIRE, 240V or 3-PHASE, 4 WIRE 208V
  • Leader pointing to inverter "RPA CONNECTION"
  • ESS SHOULD PROVIDE CONFIGURATION MODE EX: SELF CONSUMPTION
  • A production Meter is ONLY required for applications that are 40kW or greater The PV production meter will be required to have the PV generation wired to the line side terminals. Please indicate the LINE SIDE and LOAD SIDE of the PV production meter on the line diagram


ESS PROJECTS

For energy storage systems: the configuration being applied for shall be clearly indicated. Please note the correct alphanumeric configuration out of the options listed in Appendix B of the technical specification manual.

See FILES SECTION "MN-ESS Appendix B.pdf"

M3 - IF ESS, a declaration of storage is required. Please upload a declaration of storage document to Salesforce from Appendix C of the Technical Specifications Manual; be sure to select the form that matches the alphanumeric configuration that will be noted on one-line.

See FILES SECTION "MN-ESS Appendix C.pdf"


#NFZ_ALL#

Electric Service Reqs

UTILITY METER MUST MEASURE 12''X18'' TO AVOID METER UPGRADE. METER UPGRADE IF DIMENSIONS ARE LESS THAN 12''X18''. THE NEW METER SHOULD BE MILBANK WITH LEVER BYPASS. LINE SIDE TAP VIA MILBANK K4977 INT LUG KIT IS ALLOWED IN AN EXISTING OR NEW MILBANK METER.

Install Reqs


Placards


Electrical Stamp Required
0
Equipment Approvals
California Energy Commission
Meter Num Req SLD 3LD
0
ESID Num Req SLD 3LD
0
Site Plan Notes

All Jobs [24/7 UNESCORTED KEYLESS ACCESS SHALL BEPROVIDED TO ALL XCEL ENERGY EQUIPMENT // UTILITY METER AND UTILITY AC DISCONNECT MUST BE WITHIN 10' OF ONE ANOTHER AND READILY ACCESSIBLE]

Overhead [No overhead clearance issues]

Underground [No overhead service lines exist]

Label Page Notes


Electrical Diagram Notes

All Jobs [-PHOTOVOLTAIC SYSTEM CONNECTED YELLOW WITH BLACK LETTERING PLACARD TO BE LOCATED ON MAIN BILLING METER // -UTILITY PV AC DSICONNECT YELLOW AND BLACK LETTERING PLACARD TO BE LOCATED ON UTILITY PV AC DISCONNECT// -DER EQUIPMENT IS SINGLE PHASE, 240V AND UL LISTED // -AC DISCONNECT IS WITHIN 10FT OF UTILITY METER // -UTILITY ACCOUNT#: ###########]

Website
link

Other details

Restrict Inspection
0
Revision Required
1
Mod Swap Requires Planset
1
Express Planset Eligible
No