Solar Sanity Checksolar, decoded Independent. Nothing you type leaves your browser.

City of Columbia (Columbia Water & Light)

Missouri Utility Interconnection & net metering rules
Net Metering Allowed1
NEM TypeMonthly
Line Taps Allowed1
Load Taps Allowed0
AC Disconnect RequiredYes

Net metering & export

Net Metering Allowed
1
NEM Type
Monthly
TOU Utility
0
Post Solar Billing Method
Net Metering
Solar Export Type
N/A
Net Excess Generation Notes

Net Metering, the customer can select the NEM type: Option (1) For solar generated energy and the utility retaining the renewable energy credits, the Customer shall receive credit per kWh equal to the customer's current applicable rate schedule. Option (2) For solar generated energy with the customer retaining the renewable energy credits, the customer shall receive credit per kWh based upon the avoided average energy market price at the Columbia pricing node (avoided cost). 

Rebates Offered
0
Deregulated
0
Allows Standby
0

Interconnection & taps

Approval Req To Install
Yes
Interconnection Level
3
Line Taps Allowed
1
Load Taps Allowed
0
Meter Aggregation Allowed
0

System size & offset

System Size Restriction Type
No Restrictions
System Size Battery Included
0
System Size Includes Existing Systems
1
Offset Type
Percentage
Offset Value
110
Offset Calculation Basis
Average
Offset Calculation Period
36
Industry Standard Watts Sqft
Not Accepted
Utility Specific Adjustments


Inverter Oversize Restrictions
0
System Offset Notes


Offset Calc Tool
Historical Usage

Metering & disconnect

Production Meter Required
No
Production Meter Position
N/A
Production Meter Labeling
N/A
AC Disconnect Required
Yes
AC Disconnect Labeling
Visible Lockable Labeled Disconnect

Plans & docs

Site Plan Reqs
  • The disconnect is required to be within 6 feet and direct line of site of the electric meter base.
Electric Service Reqs


Install Reqs
  •  CWL may require a meter base upgrade along with any PV installation. (see Attachment 2 in file section)
Electrical Stamp Required
0
Equipment Approvals
California Energy Commission
Meter Num Req SLD 3LD
0
ESID Num Req SLD 3LD
0
Site Plan Notes


Rate Schedule Link
link
Website
link
Phone
(573) 441-5528

Other details

Restrict Inspection
0
Revision Required
1
Mod Swap Requires Planset
1
Address ID
17919096
Express Planset Eligible
Yes