NHEC - New Hampshire Electric Co-op
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Annual
- TOU Utility
- 1
- Post Solar Billing Method
- Net Metering
- Solar Export Type
- Other
- Net Excess Generation Notes
a. Applicability
1. The member-generator will be the customer of record and shall be billed for Delivered Energy services under our Schedule of Rates applicable to the member-generator’s service classification (see Terms & Conditions Section J: Classification of Service.)
2. A member-generator shall be credited for Exported Energy services under the Schedule of Rates applicable to the member-generator’s service classification. A member-generator who has chosen a competitive energy supplier will not be credited the Co-op Power portion of the Exported Energy rate.
b. Annual Review
1.Following the March billing cycle each year we shall conduct a review of member-generators that have been credited, over the preceding twelve (12) months, for more Exported Energy than Delivered Energy.
i. If a dollar credit balance remains from your Exported Energy, you will receive a written notice indicating that you can continue to carry and accumulate the dollar credit balance unless you elect to receive a payment by check for the adjusted dollar credit balance on the electric account as of the end of the March billing cycle.
- Rebates Offered
- 1
- Deregulated
- 1
- Allows Standby
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 1
- Load Taps Allowed
- 1
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Offset Notes
A member-generator may not exceed a total generating capacity of up to and including one megawatt that is located behind a retail meter on your premises, is interconnected and operates in parallel with our distribution system and is used to offset your electricity requirements.
- Offset Calc Tool
- N/A
Metering & disconnect
- Production Meter Required
- Yes
- Production Meter Position
- Inv-PM-Disco-POI
- Production Meter Labeling
- Production Meter
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
Relay Meter Orientation = Over/Under
- Include supplemental notes identifying the production meter socket & utility accessible disconnect as “accessible and exterior located”.
- Include supplemental notes identifying production meter wiring terminations as “line to solar - load to utility”.
- If POI is a tap, the UM is exterior and the MSP is interior, two AC Discos are required: A Knife Blade AC Disco exterior and next to the UM and a Fused AC Disco interior next to the MSP
- Utility accessible disconnects are required for all PV interconnections
- Utility accessible disconnects shall be combined with the production meter equipment or be installed directly adjacent to or within reach of the production meter equipment
- Must show all components of the PV & battery system exactly as it will be wired by the electrician
Production Meter Requirements
- Installed at the approved height 5 - 5.5 feet to the meter center measured from grade
- Equipment terminations are wired line (top) toward solar and load (bottom) toward utility
- Equipment is spaced a minimum 10 feet from LP gas regulators or LP gas tanks
- Smart production meters not used in NH.
- Install Reqs
https://www.nhec.com/start-stop-or-transfer-services/electric-service-handbook/
- Placards
- Placards are required to be formatted with a red background and white lettering
- Net Meter label: PRIMARY NET METER - WARNING - DUAL POWER SOURCE - SECOND SOURCE FROM SOLAR PV
- Solar Generation (REC) Meter label: SOLAR GENERATION METER
- Examples are in the database files under Label Examples
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Electrical Diagram Notes
All Jobs [Production meter & utility accessible disconnect equipment shall be noted “exterior utility accessible” // Production meter wiring terminations shall be noted “line to solar - load to utility”]
- Rate Schedule Link
- link
- Website
- link
- Phone
- (800) 698-2007
Other details
- Restrict Inspection
- 0
- Revision Required
- 1
- Mod Swap Requires Planset
- 1
- Address ID
- 135812
- Express Planset Eligible
- No