Easley Combined Utilities

South Carolina Utility Interconnection & net metering rules
Net Metering Allowed1
Line Taps Allowed0
Load Taps Allowed0

Net metering & export

Net Metering Allowed
1
TOU Utility
0
Post Solar Billing Method
Net Metering
Solar Export Type
Fixed kWh
Solar Export Rate
0.04
Solar Export Value Notes
"On-Peak Energy 4.244 ¢/kWh Off-Peak Energy 2.755 ¢/kWh"
Net Excess Generation Notes

Excess generation will be credited under the Schedule A on a monthly basis. Any generation accumlated at the EOY will be paid out to the customer.

Rebates Offered
0
Allows Standby
1

Interconnection & taps

Approval Req To Install
Yes
Interconnection Level
3
Line Taps Allowed
0
Load Taps Allowed
0
Automatic Transformer Upgrade Size
0

System size & offset

System Size Restrictions
20
System Size Restriction Type
AC kW
System Size Battery Included
0
System Size Includes Existing Systems
0
Offset Type
No Restrictions
Offset Value
0
Offset Calculation Period
0
Industry Standard Watts Sqft
2
System Offset Notes

Max. 20KW or 90% of service rating whichever is less.

Offset Calc Tool
N/A

Metering & disconnect

Allowed Meter Adapter
None

Plans & docs

SLD Reqs

Panels, inverters, disconnect switch and connection point. We do not require a production meter. We encourage back feeding a breaker in the customer’s panelboard. Pierce connection in the meter base will not be allowed. Only meter bases designed for two sets of service wires can have the solar system connected in the meter base.

Electric Service Reqs

Warning: Cut meter seals are considered tampering and may incur a $500.00 charge to the customer. Seals can only be removed with an ECU employee present.

Install Reqs

Customer shall install a manual disconnect switch of the visible load break type toprovide a separation point between the AC power output of the CRG system and any Customerwiring connected to Utility’s electric system such that back feed from the CRG system toUtility’s electric system cannot occur when the switch is in the open position. The manual disconnect switch shall be mounted separate from the meter socket on an exterior surface adjacent to the meter. The switch shall be readily accessible to Utility and capable of being locked in the open position with a Utility padlock. When locked and tagged in the open positionby Utility, this switch will be under the control of Utility. 

Website
link
Phone
(864) 859-4013

Other details

Restrict Inspection
0
Revision Required
1
Mod Swap Requires Planset
1
Address ID
155175
Express Planset Eligible
Yes