Rock Hill Electric Service
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Annual
- Post Solar Billing Method
- Net Metering
- Solar Export Type
- Fixed kWh
- Solar Export Rate
- 0.04
- Solar Export Value Notes
- On-Peak Energy 4.244 ¢/kWh Off-Peak Energy 2.755 ¢/kWh
- Net Excess Generation Notes
Customer-owned renewable generation shall be first used for Customer’s own load and shall offset Customer’s demand for electricity from the Utility.
Excess generation will be credited under the Schedule A on a monthly basis. Any generation accumlated at the EOY will be paid out to the customer.
- Rebates Offered
- 0
Interconnection & taps
- Approval Req To Install
- No
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- Offset Calc Tool
- N/A
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- Allowed Meter Adapter
- None
Plans & docs
- Site Plan Reqs
Provide an overhead elevation drawing or site plan drawing of the building showing the location of the panels on the roof with the street shown for reference and property lines. Include North arrow. Include the location of any utility lines.
- SLD Reqs
The diagram must show the meter base separate from the panel.
The meter should be shown schematically as self-contained with the service passing through meter. The PV connection cannot be made inside the utility meter base. Inverters should be equipped with integrated ARC-fault and rapid shutdown per NEC 690.5.
o Add the following notes on the plans:
o Add note, “A lockable disconnect shall be located within 6’ of the utility meter on an exterior wall and accessible to
utility personnel at all times.”
o Power riser must state “In the event of a Utility power outage the PV system will automatically disconnect from the utility.” Maximum Voltage per NEC 690.7 (A-E) and circuit sizing NEC 690.8.
- Website
- link
- Phone
- (803) 329-5590
Other details
- Restrict Inspection
- 0
- Address ID
- 154110
- Express Planset Eligible
- Yes