Rusk County Electric Cooperative, Inc.
Net metering & export
- Net Metering Allowed
- 0
- TOU Utility
- 0
- Post Solar Billing Method
- Export Rate
- Solar Export Type
- Avoided Cost
- Solar Export Rate Approx
- 0.066
- Net Excess Generation Notes
The interconnection is to be made on the member’s side of the meter, where the member will have first access to their generated power. Whatever power is not used at the time of generation will go through the meter and on to the grid(excess generation). RCEC will buyback the excess generation at the wholesale rate that is set in our tariff and currently at $0.066 per kWh
- Rebates Offered
- 0
- Deregulated
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 0
System size & offset
- System Size Restrictions
- 50
- System Size Restriction Type
- DC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Offset Notes
Residential: 15 kW
System can be sized over 15 kW up to 50 kW but will require additional engineering review.
No offset requirement as long as it does not trigger any transformer upgrade; if it does a system downsize will be required or a dedicated transformer upgrade will be required. Customer can also wait for the coop to update their infrastructure but will not be until 2030s
Metering & disconnect
- Production Meter Required
- No
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Utility Disconnect Switch
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
line side tap conductors must end in a breaker or fuses not in mlo lugs in the panel.
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Website
- link
- Phone
- (903) 657-4571
Other details
- Restrict Inspection
- 0
- Revision Required
- 0
- Mod Swap Requires Planset
- 1
- Address ID
- 121123
- Express Planset Eligible
- Yes