Solar Sanity Checksolar, decoded Independent. Nothing you type leaves your browser.

Ohop Mutual Light Company

Washington Utility Interconnection & net metering rules
Net Metering Allowed1
NEM TypeAnnual
Line Taps Allowed0
Load Taps Allowed0
AC Disconnect RequiredYes

Net metering & export

Net Metering Allowed
1
NEM Type
Annual
TOU Utility
0
Post Solar Billing Method
Net Metering
Net Excess Generation Notes

In the event the energy generated by the facility exceeds the energy consumed on the member’s premises, the excess may be distributed to Ohop Mutual’s grid through Ohop Mutual’s meter, causing the member’s meter to run backward. In no case will a credit be issued for negative usage. Instead, a bill for zero usage will be issued and negative Kwh will be “banked” for usage by the member in a subsequent month. Any banked Kwh remaining on April 30th of each calendar year shall be donated to Ohop Mutual Light Company.

Rebates Offered
0
Deregulated
0
Allows Standby
0

Interconnection & taps

Approval Req To Install
Yes
Interconnection Level
3
Line Taps Allowed
0
Load Taps Allowed
0
Automatic Transformer Upgrade Size
0

System size & offset

System Size Restrictions
25
System Size Restriction Type
AC kW
System Size Battery Included
0
System Size Includes Existing Systems
0
Offset Type
Combination
Offset Value
100
Offset Calculation Basis
Historical
Offset Calculation Period
12
Industry Standard Watts Sqft
2
Offset Calc Tool
Historical Usage

Metering & disconnect

Production Meter Required
No
Production Meter Position
N/A
Production Meter Labeling
N/A
AC Disconnect Required
Yes
AC Disconnect Labeling
Utility Disconnect Switch

Plans & docs

Site Plan Reqs

Standard

Submit/Attach a site map of system on property and directions to the site.

SLD Reqs

Standard

one-line electrical diagram for proposed electrical system, including metering points in relation to Ohop’s electrical system and member’s generating system location

Electric Service Reqs
  • UL 1741, Standard for Static Inverters and Charge Controllers for Use in Photovoltaic Systems
  • UL 1703, Standard for Safety: Flat-Plate Photovoltaic Modules and Panels
  • IEEE 12621995, Recommended Practice for Qualification of Photovoltaic (PV) Modules
  • IEEE Standard 929-2000, Recommended Practice for Utility Interface of Photovoltaic Systems
Install Reqs

AC Disconnect Switch

  • An accessible, visible, lockable disconnect switch is to be provided by the Member in an appropriate circuit which is lockable in the open position only. Typically such a device will be an air switch or fused cutouts located near the point of interconnection.
Electrical Stamp Required
0
Equipment Approvals
California Energy Commission
Meter Num Req SLD 3LD
0
ESID Num Req SLD 3LD
0
Website
link
Phone
(253) 847-4363

Other details

Restrict Inspection
0
Revision Required
1
Mod Swap Requires Planset
1
Address ID
9531473
Express Planset Eligible
Yes