Cedarburg Light and Water Utility
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Monthly
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Net Excess Generation Notes
The customer shall be billed monthly on a net energy basis and shall pay the fixed charge and energy charge specified in the rate schedule under which he is served. If, in any month, the customerās bill has a credit balance of $25 or less, the amount shall be credited to subsequent bills until a debit balance is reestablished. If the credit balance is more than $25, the utility shall reimburse the customer by check upon request. Monthly credits shall be computed by taking the net excess kilowatt-hours produced times the sum of the applicable energy charge plus monthly power cost adjustment clause (PCAC).
- Rebates Offered
- 1
- Deregulated
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Supply Side Taps Allowed
- 0
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 1
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- Allowed Meter Adapter
- None
Plans & docs
- Site Plan Reqs
For all categories, the applicant shall include with the application a site plan that shows the location of the interconnection disconnect switch, adjoining street name, and the street address of the DG facility. For Category 2, 3, or 4 DG facilities, the site plan shall show the location of major equipment, electric service entrance, electric meter, interconnection disconnect switch, and interface equipment.
- SLD Reqs
"The
applicant shall include a oneāline schematic diagram with the
completed standard application form. ANSI symbols shall be
used in the oneāline schematic diagram to show the following:
(a) Generator or inverter.
(b) Point where the DG facility is electrically connected to the
customerās electrical system.
(c) Point of common coupling.
(d) Lockable interconnection disconnect switch.
(e) Method of grounding, including generator and transformer
ground connections.
(f) Protection functions and systems.
(2) The applicant shall include with the schematic diagram
technical specifications of the point where the DG facility is electrically connected to the customerās electrical system, including
all antiāislanding and power quality protective systems. The
specifications regarding the antiāislanding protective systems
shall describe all automatic features provided to disconnect the
DG facility from the distribution system in case of loss of grid
power, including the functions for over/under voltage, over/under
frequency, overcurrent, and loss of synchronism. The applicant
shall also provide technical specifications for the generator, lockable interconnection disconnect switch, and grounding and shall
attach the technical specification sheets for any certified equipment. The applicant shall include with the schematic diagram a
statement by the manufacturer that its equipment meets or exceeds
the type tested requirements for certification."
- Install Reqs
All installations shall include equipment circuit breakers, on the DG facility side of the point where the DG facility is electrically connected to the customerās electrical system, that are capable of interrupting the maximum available fault current. Equipment circuit breakers shall meet all applicable UL, ANSI, and IEEE standards.
- Placards
The applicant shall label the interconnection disconnect switch āInterconnection Disconnect Switchā by means of a permanently attached sign with clearly visible and permanent letters. The applicant shall provide and post its procedure for disconnecting the DG facility next to the switch.
- Equipment Approvals
- California Energy Commission
- Website
- link
- Phone
- (262) 375-7650
Other details
- Restrict Inspection
- 0
- Address ID
- 166359
- Express Planset Eligible
- Yes